Evaporative condenser
Definition: The amount of heat that can be dissipated per unit time is a key criterion for selection. For example, the TZN X-1000 model has a standard heat dissipation capacity of 1000 kW (at a wet-bulb temperature of 26°C).
Category:
Evaporative condenser
Keywords:
Evaporative Condenser
Evaporative condenser Details
Core Performance Parameters
Heat dissipation
Definition: The amount of heat that can be dissipated per unit time; a key selection criterion. For example, the TZXN-1000 model has a standard heat rejection capacity of 1000 kW (at a wet-bulb temperature of 26°C).
Calculation formula
Actual heat rejection = Total system heat rejection × Correction factor
Medium parameters
Condensation temperature: Typically designed at 37°C, with an outlet water temperature–wet-bulb temperature difference (cooling range) ≤ 5°C.
Refrigerant charge: For example, the TZXN-1000 model requires 153 kg of ammonia.
Structure and Configuration Parameters
Parameter Category |
Technical Specifications |
Heat exchanger tube material |
SPCC-SD carbon steel (standard) or copper tubing, stainless steel tubing (for corrosion‑resistant applications) |
Fan configuration |
Axial flow fans (individual unit power: 1.5–5.5 kW; collectively account for 60–70% of total energy consumption) |
Sprinkler system |
The circulating water pump has a flow rate of 100 m³/h (matched to a heat rejection capacity of 1,000 kW), with a coverage rate exceeding 95%. |
Frame material |
Q235-A carbon steel, hot-dip galvanized (corrosion protection; zinc coating ≥ 80 μm) |
Operational and Energy Consumption Metrics
Overall energy consumption ratio: 0.12–0.18 kW/(m³/h), including fans, pumps, and auxiliary equipment.
Example: The TZXN-1000 model has a total power of 8.2 kW (4 fans + water pump).
Water consumption index
Make-up water: 0.1–0.2‰ of the circulating water volume (for closed-loop systems), with a drift rate ≤ 0.01%.
Evaporation: Directly proportional to the amount of heat rejected; impurities must be periodically removed via the drain valve (removal rate ≥ 90%).
Maintenance Requirements
Water quality management: pH 6.5–8.5, turbidity ≤20 NTU; conduct monthly inspections.
Antifreeze measures: During winter shutdowns, drain the system or install heating coils to maintain a water temperature of ≥5°C.