Definition: The temperature difference between the inlet and outlet water. The typical range for industrial cooling towers is 10–25℃ (wet-bulb temperature 28℃)7, and the typical range for civil cooling towers is 5–8℃.
Category:
Air cooling tower
Keywords:
Air-Cooling Tower
Air cooling tower Details
Basic Performance Parameters
Cooling Water Temperature Difference (ΔT)
Definition: The difference between the inlet and outlet water temperatures. The typical range for industrial towers is 10–25℃ (wet-bulb temperature of 28℃)7, and for civil towers it is 5–8℃.
Cooling Water Flow Rate
Unit: Cubic meters per hour (m³/h). This directly determines the size of the tower. For example, the common range in industrial applications is 700–1000m³/h.
Structural Parameters
Parameter Category |
Technical Indicators |
Source |
Heat Transfer Area |
Calculated based on heat load; air volume needs to match ≥2.5kg/(m²·s) |
6 |
Fan Configuration |
Axial flow fan, power range 3–110kW (air volume 20000–500000m³/h) |
26 |
Tower Material |
Galvanized steel plate (standard) or aluminum alloy (lightweight scenarios) |
2 |
Environmental Adaptability Parameters
Wet-bulb Temperature (τ)
Design Basis: The performance of air cooling towers is based on τ=28℃; actual selection requires correction.
Cooling Range Index: The difference between the outlet water temperature and the wet-bulb temperature ≤5℃ (high-efficiency type).
Air Volume (Va)
Operation and Energy Consumption
Parameter |
Index Range |
|
Air Resistance |
80–200Pa |
Affects fan selection and energy consumption |
Fan Energy Consumption Ratio |
0.08–0.15kW/(m³/h) |
Includes variable frequency control optimization scenarios |
Noise Level |
≤75dB(A) (1m from the tower) |
Complies with GB3096-2008 standard |
Equipment Schematic Diagram