Definition: The amount of heat that can be dissipated per unit of time; a key selection criterion. For example, the standard heat dissipation of the TZN X-1000 model is 1000 kW (wet-bulb temperature 26℃).
Category:
Evaporative condenser
Keywords:
Evaporative condenser Details
Core Performance Parameters
Heat Dissipation
Definition: The amount of heat that can be dissipated per unit of time; a key selection indicator. For example, the standard heat dissipation of the TZXN-1000 model is 1000 kW (wet-bulb temperature 26℃).
Calculation Formula
Actual Heat Dissipation = Total System Heat Dissipation × Correction Factor
Medium Parameters
Condensation Temperature: Usually designed to be 37℃, outlet water temperature and wet-bulb temperature difference (cooling range) ≤5℃.
Refrigerant Charge: For example, the TZXN-1000 model requires 153 kg of ammonia.
Structure and Configuration Parameters
Parameter Category |
Technical Specifications |
Heat Exchanger Tube Material |
SPCC-SD carbon steel (standard) or copper tubes, stainless steel tubes (corrosion-resistant scenarios) |
Fan Configuration |
Axial flow fan (single unit power 1.5-5.5 kW, total power accounts for 60-70% of total energy consumption) |
Spray System |
Circulating water pump flow rate 100m³/h (matching 1000kW heat dissipation), coverage rate exceeds 95% |
Frame Material |
Q235-A carbon steel hot-dip galvanized (anticorrosive treatment, zinc layer ≥80μm) |
Operation and Energy Consumption Indicators
Comprehensive Energy Consumption Ratio: 0.12-0.18kW/(m³/h), including fans, water pumps, and auxiliary equipment.
Example: TZXN-1000 model total power 8.2kW (4 fans + water pump).
Water Consumption Indicators
Supplementary Water: 0.1-0.2‰ of circulating water (closed system), drift rate ≤0.01%.
Evaporation: Positively correlated with heat dissipation, impurities need to be removed regularly through the drain valve (removal rate ≥90%).
Maintenance Requirements
Water quality management: pH value 6.5-8.5, turbidity ≤20NTU, monthly inspection;
Anti-freezing measures: Drain water or install heating coils when shutting down in winter (keep water temperature ≥5℃).