Products
Spray cooling tower
Single-tower flow rate: 100–1050 m³/h (WPYL series), with up to 6 units; maximum capacity can reach 6,000 m³/h (modular configuration).
Category:
Spray cooling tower
Keywords:
Spray Cooling Tower
Spray cooling tower Details
Flow and Operating Parameters
Cooling water flow rate range
Single-tower flow rate: 100–1,050 m³/h (WPYL series); up to 6,000 m³/h (modular configuration).
Typical model:
WPFL-100: 100 m³/h (inlet pipe diameter DN150, outlet pipe diameter DN200)
WPYL-400T: 400 m³/h (overall height 4,830 mm, operating weight 2,440 kg)
Temperature parameter
Standard operating conditions: Inlet water temperature 37–40°C → Outlet water temperature 32°C, wet-bulb temperature 28°C (temperature drop of 5–8°C).
High-load operating conditions: Inlet water temperature 43–60°C → Outlet water temperature 33–35°C, with a temperature drop of 10–25°C (requires special design).
Structural Design Parameters
Atomization system
Nozzle pressure: 0.035–0.15 MPa (low-pressure atomization, energy savings of 30–50%)
Atomization droplet size: ≤0.3 mm fine water droplets (enhances heat transfer efficiency)
Atomization device: filler-free design, with an internal cavity structure that reduces resistance and increases airflow.
Wind Turbines and Power
Fan airflow: 88,000 m³/h (WPFL-100) to 161,000 m³/h (WPFL-250)
Motor power: 0 kW (some models are motorless and driven by water pressure) to 7.5 kW (WPFL-250)
Tower dimensions
Typical model dimensions:
WPFL-100: 4700×3000×height unspecified
WPYL-100T: 2600×2600×4830 mm (Length × Width × Height)
Material and Weight
Material Properties
Tower Body: All‑glass fiber construction (corrosion‑resistant, aging‑resistant)
Nozzles and piping: Made of ABS or fiberglass (clog‑resistant and corrosion‑resistant)
Weight parameter
Operating weight: 2,260 kg (100T model) to 5,250 kg (300T model)
Unladen weight: approximately 860 kg (for small towers) to several tons (for large industrial towers)
Performance Advantages
Energy-saving features
Overall energy savings of 30–50% (no motor-driven fans; driven by water pressure)
Low-pressure distribution head (0.035 MPa), reducing system energy consumption.
Noise reduction capability
Noise ≤ 60 dB(A) (without motor, reducing mechanical vibration sources)
Suitable for quiet environments such as urban residential areas and hospitals.
Environmental adaptability
Typhoon-resistant design (capable of withstanding a Category 12 typhoon)
Cold-resistant (freeze-protection measures are required in northern regions)
Key selection parameters
Parameter |
Reference value |
Note |
Cooling water volume |
100–1050 m³/h (single tower) |
Supports multi-tower parallel expansion. |
Inlet water temperature |
≤60℃ (special operating conditions) |
High-temperature water requires a custom-designed atomization module. |
Wet-bulb temperature |
≤28℃ (standard design) |
Parameters need to be corrected in high-humidity regions. |
Atomization pressure |
≥0.03 MPa (WGPL series) |
Water quality impurities ≤ 10 mm |
Equipment Diagram

Prev
Next
Prev
Next
Related Products
Online consultation
Contact Us
Address:Anqiu City, Weifang City, Shandong Province, China